Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 1000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S/N
|
Name
|
Unit
|
Data
|
||
1
|
Rated voltage
|
kV
|
72.5
|
||
2
|
Rated power frequency withstand voltage (1min)
|
To earth, Between phases
|
kV
|
160
|
|
Across open contacts
|
160+42*
|
||||
3
|
Rated lightning impulse withstand voltage
|
To earth, Between phases
|
kV
|
350
|
|
Across open contacts
|
350+60*
|
||||
4
|
Rated frequency
|
Hz
|
50
|
||
5
|
Rated current
|
A
|
3150
|
||
6
|
Rated short-circuit breaking current Isc
|
kA
|
31.5
|
40
|
|
7
|
Rated short-circuit marking current (peak)
|
kA
|
80
|
100
|
|
8
|
Rated short-time withstand current
|
kA
|
31.5
|
40
|
|
9
|
Rated peak withstand current (peak value)
|
kA
|
80
|
100
|
|
10
|
Rated out-of-phase breaking current
|
kA
|
8
|
10
|
|
11
|
Short - line fault breaking current
|
kA
|
90%Isc, 75%Isc
|
90%Isc, 75%Isc
|
|
12
|
Double earch fault breaking current
|
kA
|
27.4
|
34.8
|
|
13
|
Number of rated short-circuit breaking current
|
Times
|
24
|
20
|
|
14
|
Rated duration of short - circuit
|
s
|
4
|
3
|
|
15
|
First pole to clear factor
|
|
1.5
|
1.5
|
|
16
|
Rated line charging breaking current
|
A
|
10
|
10
|
|
17
|
Rated operating sequence
|
|
O-0.3s-CO-180s-CO
|
||
18
|
Rated SF6 gas pressure/Gas refilling alarm pressure/Operation lockout pressure (gauge pressure, 20ºC)
|
MPa
|
0.4/0.36±0.015/0.32±0.015
|
||
19
|
Annual leakage of SF6 Gas
|
%
|
≤0.5
|
||
20
|
SF6 gas humidity content (mL/L) (20ºC at handover)
|
mL/L
|
≤150×10-6
|
||
21
|
Mechanical life
|
Times
|
10000
|
||
22
|
Opening time
|
ms
|
≤40
|
||
23
|
Closing-Opening time
|
ms
|
≥70 (when running)
|
||
24
|
Creepage distance
|
To earth
|
mm
|
≥2585
|
|
Across open contacts
|
≥2248
|
||||
25
|
Weight of SF6 gas filled for one set of CB
|
kg
|
8
|
||
26
|
Weight of one set of CB
|
1300
|