KYN28A air-insulated metal-clad withdrawable switchgear 3-phase AC 50/60Hz. It is mainly used to receive and distribute 7.2~24kV network electrical and control protection and monitoring to line circuit.
The cabinet is equipped with VS1 , Vacuum circuit breaker, also can be equipped with imported VD4 vacuum circuit breaker and VC series vacuum contactor.
Technical Parameter Of Switchgear
No |
Name |
Unit |
Data |
|||
1 |
Rated voltage |
kV |
12 |
15 |
24 |
|
2 |
Insuation level |
Lightning impulse withstand |
kV |
75/85 |
90/105 |
125/150 |
1min power frequency |
kV |
42/48 |
48/55 |
55/65 |
||
3 |
Rated frequency |
Hz |
50/60 |
|||
4 |
Rated current |
A |
630,1250,1600,2000,2500,3150, |
|||
5 |
4s short time withstand current |
kA |
20,25,31,31.5,40,50 |
|||
6 |
Rated peak withstand current |
kA |
50,63,80,100,125 |
|||
7 |
Thickness |
|
|
|||
7.1 |
Base frame |
mm |
2.0 |
|||
7.2 |
Side panels |
mm |
2.0 |
|||
7.3 |
Top cover(with provisions of louvers for |
mm |
2.0 |
|||
7.4 |
Doors |
mm |
2.0 |
|||
8 |
Live cable indicators for incoming & |
|
Supply Live display |
|||
9 |
Material |
|
Steel sheet coated with |
|||
10 |
Protection level |
|
Enclosure IP4X,partition of |
|||
11 |
Standard |
|
IEC62271-200 |
|||
12 |
Color |
|
RAL7032 / RAL7035 |
The enclosure and partition of the switchgear is made of top quality imported aluminum-clad galvanized steel sheet through multiple edge-folding processing with CNC machine tool. The assembled switchgear could keep uniform in dimension, and it has high corrosion resistance and oxidation resistance and higher mechanical strength than equal steel sheet. The switchgear is divided to handcart chamber ( circuit breaker chamber ), bus chamber , cable chamber and relay instrument chamber ( LV chamber ) each unit enclosure are independently earthing.
The enclosure and partition of the switchgear is made of top quality imported aluminum-clad galvanized steel sheet or steel sheet through multiple edge-folding processing with CNC machine tool. The assembled switchgear could keep uniform in dimension. Aluminum-clad galvanized steel sheet has a strong corrosion resistance and oxidation resistance, and higher mechanical strength than qual steel sheet. The switchgear is divided to handcart chamber ( circuit breaker chamber ), bus chamber , cable chamber and relay instrument chamber ( LV chamber ) each unit enclosure are independently earthing .The door of switchgear are using electrostatic spraying to make the surface with the advantage of anti impact, corrosion resistance, beautiful appearance (color can be set by the user) etc..
|
Description |
12(15)kV |
24kV |
Height(B) |
Cabinet |
2300mm |
2430mm |
Width(A) |
Branch bus current less than 1600A, short circuit break current at 31.5kA |
800mm |
1000mm |
Branch bus current more than 1600A |
1000mm |
1000mm |
|
Depth(C) |
Cabinet |
1500mm |
1860mm |
Weight(kg) |
800~1200 |
A Handcart
The truck frame series adopts thin steel plate by CNC machine after processing by riveting, welding to make it. According to the use of handcart, which can be divided into circuit breaker handcart, voltage transformer handcart, isolator handcart, metering handcart, etc.. The handcart with same purpose could convenient to exchange.The handcart has the isolation position, the test position and the work position in the cabinet, each position is provided with the positioning device, so as to ensure that the handcart can not move freely when the position is in above , while moving handcart, it must be unlocked
B Bus room
The bus bar is led from one switchgear to another switchgear by branch bus bar and static contact box to fix. The flat branch bus bar is connected with the static contact box and main bus bar by bolts, and it does not need any other wire clip or insulator connection. When the user and the special needs of the project, the busbar connection bolts can be insulated and end cap packaging. When the bus across clapboard of the switchgear by bus bushing to fix. If an internal fault arc occurs, the accident can be limited to extend to the adjacent panel and the mechanical strength of the busbar can be ensured.
C Cable room
An cable room could install current transformer, grounding switch, arrester and cable, and at the bottom of the preparation of slotted removable aluminum plate to ensure the construction site conveniently.
D relay instrument room
The relay instrument room is used to install all kinds of relays, instruments, signal indication, operation switch and other components. In addition, according to user requirements for adding a small bus room in the top of the instrument room , and can lay of sixteen loops controlling small bus .
Lock structure
Connection between the door and the cabinet with lock structure, and with the lifting mechanism to make it more convenient for opening the door, when medium door is in the closed state, which is connected with a strength of the cabinet body, strengthens the ability to effectively combat internal arcing fault.
The switchgear has reliable interlock device, which provides reliable safety and protection for operators and equipment , its function as follow:
1 When the grounding switch is in open position, the handcart can move from the test position to service position.
2.The handcart of the circuit breaker has been fully engaged in the test or service position before operation.
3.Handcart is in the service position, the secondary plug is locked and can not be removed.
4.The grounding switch is closed, the handcart cannot from the test position move to service position .
5.Grounding switch can only be operated when the handcart is in the test position or isolated position. The switchgear can be equipped with an electromagnet locking mechanism in the grounding switch operating mechanism to improve the reliability to prevent high voltage charged and misoperation grounding switch. Its order can be according to the user's needs.
The secondary wires of the switchgear is connected with the secondary of the handcart through the manual secondary plug. The movable contact of the secondary plug is connected by the handcart and a nylon corrugated telescopic pipe, and the secondary static contact seat is arranged on the upper right side of the handcart compartment of the switchgear. Handcart is only in the test position and then can plug and remove secondary plug. When the handcart is in the service position, the secondary plug is locked and can not be removed ,because of the interlocking mechanism.
In a separate cable room install 8 x 40mm grounding bus bar, this row can run through the adjacent cabinet and good contact with cabinet, this ground row directly grounding for components using, at the same time ,as the whole cabinet with aluminum-clad galvanized steel sheet combining together, so that the entire cabinet are in good grounding state to ensure the safety operator touching cabinet .