Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Manual Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Vacuum |
Installation: | Fixed |
Structure: | Vacuum |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
ZW32-12 11KV 400A Outdoor pole-mounted vacuum automatic recloser
Item |
Description |
Actual |
1 |
Type/Designation |
Outdoor pole-mounted type |
2 |
Interrupting medium |
Vacuum |
3 |
Country of origin |
China |
4 |
Voltage rating |
|
4(i) |
Nominal |
11KV |
4(ii) |
Maximum |
15 KV |
4(iii) |
Power frequency |
50 /60 HZ |
4 (iv) |
Basic Insulation Level |
95 KV |
5 |
Current rating |
|
5(i) |
Continuous Load Current |
400A |
5(ii) |
Short time 3 seconds |
8 KA |
5(iii) |
Interrupting |
8 KA |
5(iv) |
Closing and latching capability |
20 KA |
6 |
Interrupting cycles |
20 000@400A |
7 |
Opening time (trip initiation to contact open) separation) |
50 ms |
8 |
Closing time (close initiation to contact make) |
90 ms |
9 |
Duty Cycle |
O-0.3s-CO-3mins -CO |
10 |
Type of Operating Mechanism |
|
|
- Trip mechanism |
Magnetic
|
|
- Closing mechanism |
Magnetic
|
11 |
Type of control |
Microprocessor |
12 |
Number of operations to Lockout |
4 |
13 |
Number of fast operations |
Programmable |
14 |
Number of slow operations |
Programmable |
15 |
Accessories |
|
|
- Bushing ct's |
3 nos bushing CT (current transformer) |
|
-Statistical Metering Facility |
yes |
|
- Remote trip |
yes |
|
- Remote close |
yes |
16 |
Dimensions |
|
|
- Height |
930 mm |
|
- Width |
1090 mm |
|
- Depth |
230 mm |
|
Gross weight (in a single wooden box) |
123 kgs |
17 |
SCADA Compatible |
yes |
18 |
Manufacturer |
Boerstn Electric co.,ltd |
19 |
Country of origin |
China |
20 |
Recloser unit complete with a voltage transformer: Yes/No |
Yes, with one VT-voltage transformer |
Suppliers with verified business licenses