High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A

Product Details
Customization: Available
Shell Material: Stainless Steel
Voltage Level: Medium Voltage
Still deciding? Get samples of US$ 1500/Piece
Request Sample
Manufacturer/Factory, Trading Company
Gold Member Since 2019

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO 9001, ISO 14001
Export Year
2010-10-01
  • High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A
  • High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A
  • High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A
  • High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A
  • High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A
  • High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A
Find Similar Products

Basic Info.

Model NO.
KYN61-40.5
Installation
Removable
Structure
Cabinet
Current
AC
Transport Package
Track
Trademark
JUNKE
Origin
China
HS Code
8538909000
Production Capacity
1000PCS

Product Description

High Voltage Withdrawable VS1 vacuum breaker metal clad Switchgear KYN61-40.5KV
vs1 vocuum circuit breaker 
SF6 Sulphur hexafluoride
1. Cabinet structure adopts assembly type, circuit breaker adopts handcart floor type structure;
2. Fitted with completely new type of composite insulation of vacuum circuit breaker, and has good compatibility and replace simply characteristic;
3. Handcart frame is provided with a screw nut propelling mechanism, which can be easily moved by the hand cart, and can prevent the damage of the pushing structure from the misoperation ;
4. All operations can be carried out when the door closed;
5. Main switch, trolley, interlock between switchgear door adopts the mandatory mechanical locking to meet "five protection" function;
6. The space of cable room is ample, and can connect a plurality of cables;
7. The quickly earth switch for grounding and line circuit short circuit;
Vacuum Switchgear mainly technical parameters

No

Description

Unit

Data

1

Maximum system voltage

kV

40.5

2

Rated Voltage

kV

30,33,36

3

Rated Current

A

630 ,1250 ,1600,2000,2500,3150,4000

4

Rated Frequency

Hz

50/60

5

Rated short-time withstand current

kA

25,31.5,40

6

Rated Peak withstand current

kA

50,63

7

Rated power frequency withstand voltage

kV

85/1min

8

Rated impulse lightning withstand voltage

kV

185

9

Rated short circuit duration

s

4

10

Protection level

 

IP4X


Vacuum Circuit Breaker Main Technical Parameters

No

Description

Unit

ZN85 Data

1

Rated Voltage

kV

40.5

2

Rated Current

A

630 ,1250 ,1600,2000,2500,3150

3

Rated Frequency

Hz

50/60

4

Rated short-time withstand current

kA

25,31.5,40

5

Rated short circuit break current

kA

25,31.5,40

6

Rated Peak withstand current

kA

50,63

7

Rated power frequency withstand voltage

kV

85/1min

8

Rated impulse lightning withstand voltage

kV

185

9

Rated short circuit duration

s

4

10

Open time

ms

30≤t≤60

11

Close time

ms

50≤t≤100

12

Rated short circuit break current numbers

 

2

13

Mechanical Endurance

Times

10000


Spring operating mechanical main technical parameters
 

No

Description

Unit

Data

1

Rated Voltage

Open coil

V

DC220/110 AC220/110

Close coil

2

Rated operate current

Open coil

A

0.96(220 V) 1.05(110V)

Close coil

3

Spring charge motor

W

230

4

Spring charge motor rated voltage

V

DC220/110 AC220/110

5

Spring charge time

S

≤12

  • 1. Enclosure and partition
    The Enclosure and partition plate of the switchgear is made of cold rolled steel plate after being processed by a numerical control machine and bolting by benting . As a result, the assembled switchgear can ensure the unity of the structural dimensions. Switchgear is divided into circuit breaker chamber, the main bus chamber, cable chamber and the relay instruments chamber, each parts to be separated by a grounded metal partition.

  •  
  • 2. Handcart
    According to handcart using purpose , it can be divided into the circuit breaker handcart , the voltage transformer handcart , measuring handcart isolation handcart , etc., all kinds of handcart outline dimension is same , the using purpose of handcart with interchangeability. Handcart has test /isolation position and service position, each position is equipped with interlocking devices to ensure that the handcart can not move when it is in above test /isolation position and service position.

  •  
  • 3.Circuit Breaker Compartment
    The circuit breaker compartment is fitted with the necessary guide rails to accommodate the withdrawable part,which can be moved between the service position and the test position. The isolation valve is automatically opened or closed to ensure staff not touch the charged body.The withdrawable part can be operated when the door of panel closed.through the observation window to see the handcart in the cabinet position , at the same time to see any function signs on the handcart.

  •  
  • 4.Bus Compartment
    Main bus are laid in sections from panel to panel by branch small bus and fix contacts box to fix .Across side board of the adjacent cabinet with bus bushing to fix. All buses adopt composite insulation.

  •  
  • 5. Cable Compartment
    Cable compartment can be installed PT, earthing switch, lightning arrester and a plurality of cables.

  •  
  • 6. Relay Compartment
    Relay compartment inner board and panels can be installed to control, protection components, measurement, display instruments, live monitoring indicators etc secondary components.

  •  
  • 7. Interlocks device
    Switchgear has reliable interlock device to ensure the safety of operators and equipment:
    When the earthing switch in the off position, the truck can move from the test / disconnected position to the service position and the back door can not be opened to prevent accessing into live space.
    When the truck pulled completely out of cabinet outside or truck in the test/isolation position in the cabinet and the earthing switch interlocking can unlock , the earthing switch can close operation; The truck is in the working position, earthing switch can not be closed to prevent the earthing switch mal-closing with the electrification and prevent the earthing switch in the closed position when the truck moved to the service position.
    The circuit breaker truck in the test / disconnected position or working position, we can operate circuit breaker ; after circuit breaker closed ,the truck can not move to prevent mal- pushing and mal-pulling circuit breaker under charged load
    The electric interlocking can be installed between cabinets .

  •  
  • 8.Earthing device
    In the cable chamber, alone with Φ6× 50mm2 grounding bus, which can run through the adjacent cabinets, and good contact with cabinets

    Switchgear Outline Dimension

    High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A

    Outline dimension (W×D×H)mm:

    Switchgear structure sketch

    A Relay instruments chamber

    B Bus chamber

    1400×2800×2600

    C Circuit beaker chamber

    D Cabl e chamber

    1200×2800×2400

    1200×3000×2600

    Switchgear Installation

  •  1.Height of electrical room: ≥4500mm;
    2. Distance from cabinets back to wall: ≥1500mm;
    3. Basic frame of flatness: ≤1 mm/m2;
    4.Based on embedded channel higher ground shall not exceed 3mm;
    5. Available bolts or welding can be fixed on the foundation;
    6. Switchgear weight about :1800Kg;
    7. Switchgear operating corridor width (single row): ≥3000mm,double row (face to face ) ≥4000mm. 
  • Schematic Diagram Of Switchgear Installation Foundation

High Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000AHigh Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000AHigh Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000AHigh Voltage Withdrawable Vs1 Vacuum Breaker Metal Clad Switchgear Kyn61-40.5kv 630-4000A

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier