| Rated current of frame Inm | 630 | 1000 | 1600 | 2500 | 4000 | |||
| (A) | 200 | 400 | 630 | 1000 | 1600 | 2500 | 4000 | |
| Conventional thermal current Ith(A) | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
| Rated current of breaker In(A) | A hot electromagnetism type | 100 160 200 |
315 400 | 315 400 630 |
630 800 1000 |
1600 | 1600 2000 2500 |
2500 3000 4000 |
| Electronic type | 100 200 | 200 400 | 315 400 630 |
630 800 1000 |
1600 | 1600 2000 2500 |
2500 3000 4000 |
|
| Rated capacity of short circuit breaker(kA) | AC 380V | 20 | 30 | 30 | 40 | 40 | 60 | 80 |
| AC 660V | 25 | 25 | ||||||
| AC 1140V | 12 | 12 | ||||||
| Rated short time current(kA) | 8 | 12.6 | 12.6 | 30 | 30 | 40 | 60 | |
| time about rated short time current (S) | 0.2 | 0.2 | 0.2 | 0.5 | 0.5 | 0.5 | 0.5 | |
| mechanical endurance of breaker | 10000 | 10000 | 10000 | 5000 | 5000 | 5000 | 5000 | |
| electrical endurance(1In,1Ue)(times) | 1000 | 1000 | 1000 | 500 | 500 | 500 | 500 | |
| AC380V Protection electrical enduranceAC-3(times) | 2000 | 2000 | 2000 | |||||
| frequency of operation | 60 | 60 | 60 | 20 | 20 | 20 | 20 | |
| Fly arcly Distance (mm) | 280 | 280 | 280 | 350 | 350 | 350 | 350 | |
| arm of force operation (mm) | 90 | 90 | 90 | 250 | 250 | 250 | 250 | |
| operation force(N) | 200 | 200 | 200 | 350 | 350 | 350 | 350 | |