Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 1000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Installation site
|
outdoor
|
Ambient temperature
|
-25ºC~+40ºC
|
Max. daily temperature difference
|
≤25ºC
|
Height above sea level
|
2000m(no limit for specified order)
|
Air humidity
|
Daily average:≤95%; month average:≤90%; |
Wind speed
|
≤34m/s
|
Solar radiation
|
≤0.1W/cm2(fine day, noon)
|
Earthquake intensity
|
horizontal:≤0.3g;vertical:≤0.15g
|
Icing thickness
|
≤10mm
|
Creepage distance
|
25mm/kV or 31mm/kV
|
Static load on terminal in Y-direction
|
1250N
|
Static load on terminal in X-direction
|
750N
|
Static load on terminal in Z-direction
|
1000N
|
No.
|
Items
|
Unit
|
Parameter
|
||
1
|
Rated voltage
|
kV
|
110KV
|
||
2
|
Rated power frequency withstand voltage(1min)
|
Phase-to-phase Phase-to-ground |
kV
|
230
|
|
fracture
|
kV
|
230+73*
|
|||
3
|
Rated lightning impulse withstand voltage
|
Phase-to-phase Phase-to-ground |
kV
|
550
|
|
fracture
|
kV
|
550+103*
|
|||
4
|
Power frequency withstand voltage(5min)under SF6 zero-gauge pressure
|
kV
|
95
|
||
5
|
Rated frequency
|
Hz
|
50
|
||
6
|
Rated current
|
A
|
3150
|
||
7
|
Rated short circuit breaking current
|
kA
|
40
|
||
8
|
First-pole-to-clear factor
|
|
1.5
|
||
9
|
Rated short circuit breaking current (DC component) |
|
More than 41%
|
||
10
|
Rated short circuit making current (peak)
|
kA
|
100
|
||
11
|
Rated short time withstand current(rms)
|
kA
|
40
|
||
12
|
Rated peak withstand current
|
kA
|
100
|
||
13
|
Rated short circuit duration
|
s
|
4
|
||
14
|
Rated out-of-phase breaking current
|
kA
|
3(OP1) ,10(OP2)
|
||
15
|
Short range breaking current
|
kA
|
36;30
|
||
16
|
Wrong-phase earthing fault breaking current |
kA
|
34.8
|
||
17
|
Rated line charging switching current
|
A
|
31.5
|
||
18
|
Full capacity breaking time without check and repair
|
Times
|
20 or rated current breaking times:3000
|
||
19
|
Rated operating sequence
|
|
O-0.3s-CO-180s-CO
|
||
20
|
Rated SF6 pressure (20ºC gauge)
|
MPa
|
0.6
|
||
21
|
Alarm/Lock pressure(20ºC gauge)
|
MPa
|
0.55/0.50
|
||
22
|
SF6 annual leakage rate
|
%/Y
|
≯0.5
|
||
23
|
Gas moisture content
|
Check value after hand over |
μL/L
|
≯150
|
|
Allowed service value |
μL/L
|
≯300
|
|||
24
|
Resistance of the main circuit
|
μΩ
|
≤35
|
||
25
|
Mechanical life
|
Time
|
6000
|
||
26
|
Radio interference level (1.1Ur/)
|
μV
|
≯500
|
||
27
|
Allowed partial discharge intensity(1.2Ur)
|
pC
|
≤5
|
||
28
|
Noise(distance from sound source:horizontality:2m,height:1.5m)
|
dB
|
90
|