LW8-40.5 SF6 Circuit breaker high voltage 35KV Transmission line Tank type 35kV high voltage vacuum circuit breaker
Silicone rubber violet: heat resistance, cold resistance, dielectric resistance, ozone resistance and atmospheric aging resistance
Copper metal material: the product is made of red copper metal material and stainless steel, which is not rusty, easy to rust and good contact
Stainless steel shell: truly maintenance free performance
Item |
Description |
unit |
Data |
1 |
Rated voltage |
KV |
35 |
2 |
ceiling voltage |
KV |
40.5 |
3 |
Rated insulation level |
Lightning impulse withstand voltage (full wave peak) |
KV |
185/215() |
|
|
Power frequency withstand voltage (1 minute) |
KV |
95/118() |
4 |
Rated current |
A |
1600/2000 |
1600/2000/2500/3150 |
5 |
Mechanical life |
Times |
5000 |
5000 |
3000 |
2000 |
6 |
Mechanical life rated pressure of sulfur hexafluoride gas (gauge pressure at 20 ºC) |
Mpa |
0.35 |
0.38 |
0.45 |
0.5 |
7 |
Locking pressure (gauge pressure at 20 ºC) |
Mpa |
0.3 |
0.33 |
0.4 |
0.45 |
8 |
Minimum operating ambient temperature |
ºC |
-40 |
-30 |
9 |
Rated short-circuit breaking current |
kA |
20 |
25 |
31.5 |
40 |
10 |
Rated short-circuit making current (peak) |
kA |
50 |
63 |
80 |
100 |
11 |
Rated short-time withstand current (thermal stability current) |
kA |
20 |
25 |
31.5 |
40 |
12 |
Cumulative breaking times under rated out of step breaking current and rated short-circuit |
kA |
50 |
63 |
80 |
100 |
13 |
breaking current |
kA |
5 |
6.3 |
8 |
10 |
14 |
Closing time (under rated operating voltage) |
Times |
15 |
15 |
10 |
10 |
15 |
Opening time (under rated operating voltage) |
s |
<0.1 |
16 |
Rated operating sequence |
s |
<0.06 |
17 |
Rated opening and closing current of single capacitor bank |
|
Open-0.3s-close open-180s-close open |
18 |
Rated short circuit duration |
A |
400 |
19 |
Annual air leakage rate |
s |
4 |
20 |
Moisture content of sulfur hexafluoride gas (at 20 ºC) |
%/year |
<1 |
21 |
Rated operating voltage of ct14 spring operating mechanism |
Ppm(v/v) |
<150 |
22 |
Voltage of closing coil and opening coil |
v |
AC 220/380V DC 48 110V 220V |
23 |
Energy storage motor voltage |
v |
AC 220V ,DC220V |
24 |
Sulfur hexafluoride gas weight |
kg |
8 |
25 |
Weight of circuit breaker (including operating mechanism) |
kg |
1400 |
LW8-40.5KV AIR CIRCUIT BREAKER